Molded Case Motor Circuit Protector (MCP), Ex9M4M Series, MCCB
600 A Frame Size, S Interrupting – Lug Line/ Load Side Connection
3 Poles,600A
Part number: 1101528
Full Load Current at Cam Setting & Trip Settings:
A-230.8 to 276.8 A, Trip 3000
B-276.9 to 323.0 A, Trip 3600
C-323.1 to 369.0 A, Trip 4200
D 369.2 to 415.3 A, Trip 4800
E-415.4 to 461.4 A, Trip 5400
F-461.5 to 507.6 A, Trip 6000
G-507.7 to 522.2 A, Trip 6600
Rated Current at 480Vac 42kA
Features:
The traditional system used for this purpose is based on three different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase loss or unbalance of phase, and a contactor for motor switching.
In particular, when selecting these devices, different factors must be taken into consideration, such as:
The motor power, The diagram and type of starting, The type of motor: with cage rotor or with wound rotor, The fault current at the point of the network where the motor is installed
Certifications:
UL 489 Recognized, File Number E355392 (Standard for connection terminals which allows the user to apply field wiring directly to the breaker)
Certified for Canada According to CSA Standards 22.2 No.5
IEC/EN 60947-2
CE Compliant